Dry Type Distribution Transformers
Cast resin dry type distribution transformer builds for indoor installation. Fire-safe, low noise, built to IEC 60076.
Technical specification
| Power Rating | 50 – 6000 kVA |
|---|---|
| Primary Voltage | 3.3 / 6 / 10 / 11 / 13.2 / 13.8 / 15 / 20 / 22 / 33 / 34.5 / 35 kV class |
| Secondary Voltage | 480/277 V, 400/230 V, 380/220 V, or customized |
| Phase | Three-phase |
| Cooling Type | AN |
| Core Material | High-efficiency (CRGO) silicon steel |
| Connection Group | Dyn11, Yyn0, Dyn5 |
| Winding Material | Copper / Aluminium |
| Frequency | 50 / 60 Hz |
| Insulation | Cast resin (dry type) |
| Tap Changer | ± 2 × 2.5% Off-Circuit Tap Changer (OCTC) |
| Short-circuit impedance | 4 – 6% |
| Temperature Rise | 60 – 65 °C |
| Noise Level | ≤ 60 dB at 1 meter |
| Enclosure | Optional sheet-steel enclosure, IP00 to IP54 |
| Altitude | ≤ 1,000 m or customized |
| Ambient Temperature Range | -30 °C to +50 °C |
| Accessories | Conservator tank, oil level indicator, gas relay, pressure relief valve, etc. |
| Standards Compliance | IEC 60076, IEEE C57, ANSI C57 |
| Applications | Commercial and institutional buildings, industrial facilities, oil & gas, solar and wind energy, utility grid connections, data centers, and coastal islands and high-altitude regions. |
| Transport & Installation | Lifting lugs, skid base, galvanized fittings |
| Warranty | Two years |
| Delivery Time | Typically 30 days, depending on quantity |
| Min. order quantity | ≥ 1 set |
Typical ratings
50 · 100 · 200 · 315 · 500 · 630 · 800 · 1000 · 1250 · 1600 · 2000 · 2500 kVA and above
Other ratings are built to order. If your rating is not on this list, send it anyway.
How it is built
- Core: grain-oriented silicon steel, mitred step-lap, treated against corrosion.
- Winding: cast resin under vacuum, copper or aluminium conductor.
- Insulation: class F, temperature rise 100 K; class H on request.
- Enclosure: IP00 to IP54, with or without a sheet-steel housing.
- Cooling: AN; forced air (AF) with a temperature controller on request.
Options and accessories
Tap changer
Off-circuit ±2 × 2.5%, or an on-load tap changer.
Winding material
Copper or aluminium, to the loss figures you need to meet.
Protection
Pressure relief device, gas relay, oil level and temperature indicators.
Terminations
HV cable box or bushings, LV busbar or cable box.
Monitoring
Winding temperature indicator with alarm and trip contacts.
Finish
Standard industrial paint, or the colour your utility specifies.
Standards and testing
- Routine tests on every unit: winding resistance, ratio and vector group, insulation resistance, impedance voltage, separate-source and induced voltage withstand.
- Type tests on request: temperature rise, lightning impulse, short-circuit withstand.
- Designed and tested to IEC 60076. IEEE and ANSI practice applied for 60 Hz designs.
- A test report in English goes out with every transformer.