Distribution Transformer

We supply distribution transformers to factories, industrial plants, manufacturing facilities, commercial buildings, hospitals, hotels and shopping malls, as well as to electrical contractors, MEP…

Talk to an Engineer

Email
info@xsdfftransformer.com

Phone
+86 158 6789 7761

WhatsApp
+852 2416 2620

A distribution transformer is the final voltage conversion step in an electrical power system: it steps medium voltage — typically 11 kV, 22 kV or 33 kV — down to a usable low voltage such as 400/415 V for motors, machinery, lighting, HVAC and building services.

We supply distribution transformers to factories, industrial plants, manufacturing facilities, commercial buildings, hospitals, hotels and shopping malls, as well as to electrical contractors, MEP contractors and transformer distributors. Whether you need a standard rating or a unit engineered around a specific load profile, the design starts from your actual demand, installed environment and local grid conditions.

Technical Specifications

ParameterTypical Value
Rated capacity500 – 3150 kVA (other ratings on request)
Primary voltage11 kV / 22 kV / 33 kV
Secondary voltage400 V / 415 V / 433 V (or as specified)
Frequency50 Hz or 60 Hz
PhaseThree phase
CoolingONAN / KNAN / AN / AF
InsulationClass A / Class F / Class H (dry type)
Winding materialCopper or aluminium
Vector groupDyn11 (other groups on request)
Impedance4% – 6% typical
Off-circuit tap changer±2 x 2.5% or ±5%
StandardsIEC 60076 / IEEE C57.12 / local grid standard
InstallationIndoor or outdoor

Typical values for this product family. Insert your certified datasheet values before publication — Hebei Youge Electrical Equipment Co., Ltd..

Applications

Advantages

Customization Options

Manufacturing, Testing and Standards

Every unit is built under documented process control and subjected to routine tests before dispatch: winding resistance, voltage ratio and vector group, impedance voltage and load loss, no-load loss and current, applied and induced voltage dielectric tests, and functional checks of accessories. Type tests — including lightning impulse, temperature rise and short-circuit withstand — are available for new designs and project requirements. See our testing and quality control pages.

Frequently Asked Questions

Sizing starts from the connected load, the diversity factor and the expected growth margin. As a working rule, add 20–30% headroom above the calculated maximum demand. Send us your load list and we will size it for you.
Oil immersed units are generally preferred outdoors and for higher ratings because of better cooling and overload capability. Dry type (cast resin or VPI) is preferred indoors, underground, in high-rise buildings and anywhere fire risk and maintenance access matter.
IEC 60076 and IEEE C57.12 are the common baselines; many projects also require a local utility or national grid specification. Tell us the destination country and we will confirm the applicable standard — Hebei Youge Electrical Equipment Co., Ltd. for our current certificate list.
Lead time depends on rating, voltage class and material choice. Hebei Youge Electrical Equipment Co., Ltd.. We will give you a firm production slot with the quotation.