Medium Voltage Transformer
Selecting a medium voltage transformer is not only about kVA.
Medium voltage transformers operate on the primary side at 11 kV, 22 kV or 33 kV — the voltage levels used for regional distribution and for large industrial and commercial intake substations.
Selecting a medium voltage transformer is not only about kVA. Insulation level (BIL), vector group, impedance, tapping range and the short-circuit withstand capability of the winding all have to match the network you are connecting to. We engineer each unit against your network data so it can be installed and energised without site modification.
Technical Specifications
| Parameter | Typical Value |
|---|---|
| Rated capacity | 500 – 3150 kVA (higher on request) |
| Primary voltage | 11 kV / 22 kV / 33 kV |
| Secondary voltage | 400 V / 415 V / 433 V / 690 V |
| Frequency | 50 Hz or 60 Hz |
| BIL / insulation level | Per IEC 60076-3 for the system voltage |
| Vector group | Dyn11, Dyn5, Yyn0 (as specified) |
| Impedance | 4% – 8% depending on fault level |
| Cooling | ONAN / KNAN / AN / AF |
| Tap changer | Off-circuit ±2 x 2.5% (OLTC on request) |
| Standards | IEC 60076 / IEEE C57.12 |
| Installation | Indoor substation, outdoor kiosk or pad mount |
Typical values for this product family. Insert your certified datasheet values before publication — Hebei Youge Electrical Equipment Co., Ltd..
Applications
- Industrial intake substations
- Factory MV/LV distribution
- Commercial building substations
- Data and process facilities
- Renewable and cogeneration connection
- Utility-style distribution points
Advantages
- Designed against your actual network fault level and BIL requirement
- Correct impedance selection to limit downstream short-circuit current
- Off-circuit or on-load tap changing to handle network voltage variation
- Compatible with RMU, switchgear and protection panels
- Suitable for indoor substations and outdoor enclosures
- Full routine testing with certified test reports
Customization Options
- Primary voltage and BIL level
- Vector group and impedance
- Off-circuit taps or on-load tap changer
- Indoor or outdoor enclosure and IP rating
- Integration with existing switchgear and protection scheme
Manufacturing, Testing and Standards
Every unit is built under documented process control and subjected to routine tests before dispatch: winding resistance, voltage ratio and vector group, impedance voltage and load loss, no-load loss and current, applied and induced voltage dielectric tests, and functional checks of accessories. Type tests — including lightning impulse, temperature rise and short-circuit withstand — are available for new designs and project requirements. See our testing and quality control pages.