Three Phase Distribution Transformer Guide

Almost all industrial and commercial power distribution is three phase. A three phase distribution transformer is one unit with three windings on a common core, more compact, more efficient and cheaper per kVA than a bank of three single phase units.

This guide covers what to specify and the mistakes that cause problems later.

Almost all industrial and commercial power distribution is three phase. A three phase distribution transformer is one unit with three windings on a common core, more compact, more efficient and cheaper per kVA than a bank of three single phase units.

This guide covers what to specify and the mistakes that cause problems later.

Why three phase

Three phase power delivers more power for the same conductor material and gives rotating machines a naturally rotating magnetic field. That is why motors, compressors, chillers and lifts are three phase, and why distribution at meaningful capacity is three phase.

Vector groups explained

The vector group describes how the windings are connected and the resulting phase shift. Dyn11 means a delta primary, a star secondary with neutral brought out, and the secondary line voltage leading the primary by 30° (11 o’clock position).

Dyn11. Most common distribution group. Delta primary blocks triplen harmonics; star secondary provides a neutral.

Yyn0. Used where a star primary is required; sensitive to unbalanced loading.

Dyn5. Alternative to Dyn11 where required by the network.

Neutral and single phase loads

A star secondary gives a neutral, so single phase loads connect between one phase and neutral. They should be spread evenly across the three phases to limit neutral current and voltage unbalance.

Paralleling transformers

Two transformers can run in parallel only if they have the same vector group, the same voltage ratio, the same phase sequence and closely matched impedance. Ignoring this causes circulating currents that waste capacity and trip protection.

Typical ratings and specifications

Rating. 500–3150 kVA

Primary. 11 kV / 22 kV / 33 kV

Secondary. 400 V / 415 V

Impedance. 4–6%

Cooling. ONAN / KNAN / AN / AF

Windings. Copper or aluminium

Frequently Asked Questions

Yes, and it is sometimes done for spare-parts simplicity in rural networks. For industrial and commercial sites a single three phase unit is normally cheaper, smaller and more efficient.

Neutral current rises, one winding runs hotter than the others, and voltage unbalance can cause three phase motors to overheat. Balance single phase loads across phases.

Yes, single phase loads are connected phase to neutral, distributed across the three phases.